PRIMATRON STEAM BOILER

A Three Pass Combined Flue and Smoke Tube Boiler

The flame of the burner penetrates deep into the closed end of the combustion chamber and then reverses back to the front of the boiler into the flame tubes.

  • The first phase of heat exchange process is by radiation during the combustion process.

  • The second phase occurs when this combustion gas reverses direction enveloping the flames.

  • The third phases of heat exchange process is the same as the second phase but by convection. It occurs along the smoke tubes.
Advantages:

  • The reverse flue covers the main flame from the burner preventing overheating in combustion chamber.

  • It has a turbulator inside the flame tubes, which produces turbulence that result in a better combustion efficiency.

  • It has economical value because of its simple construction.
Our Primatron Steam Boiler ranges from 1,000 kg/hr up to 5,500 kg/hr.

Standard Specification



MODELYB-20YB-25YB-32YB-40YB-50YB-60YB-80YB-110
Steam Capacity (kg/hr)1,0001,2501,6002,0002,5003,0004,0005,500
Design Pressure, up to (kg/cm²)3030303030303030
Dimension (mm)        
A23852824317634313676359642224376
B16801750185020002100224024102550
C19202130223023802480260727972970
D19301900200022002400239026102700
E300300350350390450500650
Weight Empty (ton)3.323.905.126.287.648.7310.9111.19
*Fuel Consumption
Light Oil (ltr/hr)71.789.7114.8143.4179.3215.2286.9394.5
Natural Gas ( Nm³/h)72.190.1115.4144.2180.3216.3288.4396.6
*) Based on 85°C, 9 barg Operation