In the Pyrocondens® Condensation Boiler processing system:
  • Water vapors is generated in the flue gas which is then is cooled into condensate

  • Heat obtained during the condensation process is absorb by the boiler


This unique method translates into an efficiency level of up to 6% during oil combustion (compare to the conventional Hot Water Boiler) and 11% during gas combustion.

Bottom line: This particular boiler can operate at efficiency level of 95% - 98%! That's almost the perfect rate for boiler!



Technical Specification

Type 50 75 100 150 200 250 300
Capacity (kW) Max. 50 75 100 150 200 250 300
Dimension (mm) l
w
h
810
530
1574
1000
630
1786
1000
630
1786
1130
760
1897
1130
760
1897
1270
790
1967
1270
790
1967
Chimney e
f1
d2
123
50
456
183
30
492
183
30
492
253
65
525
253
65
525
303
65
544
303
65
544
Outlet (DN)

Inlet (mm)
g
r1
r2
s2
40
1473
532
140
50
1679
532
180
50
1679
532
180
65
1784
532
225
65
1784
532
225
80
1847
532
255
80
1847
532
255
Dimension (mm) L
W
H
917
687
1585
1110
808
1796
1110
808
1796
1245
951
1905
1245
951
1905
1377
1058
1975
1377
1058
1975
Design Pressure (bar) 4 4 4 4 4 4 4
Water Content (liter) 87 160 160 242 242 343 343
Weight (kg) 290 455 465 565 575 720 735
Water Pressure Drop (mbar) DPw 2 3 5 10 17 17 24
Minimum Flow Rate (m3/h) 1.5 1.9 1.9 3.4 3.4 5.0 5.0
Flue Gas Pressure Drop (mbar) DPa 0.75 0.65 0.5 1.00 1.80 1.25 1.80


Request for more information